The 2024 update introduces several critical shifts in how electrical systems are designed and verified: nuova norma cei 64-8 - CNI
For TN systems, the maximum intervention time for socket circuits greater than 32 A has been reduced from 5 seconds to 0.4 seconds (and 0.2 seconds in special environments). Switchgear and Controls (Chapter 46):